- Air Washers / AHU
- Pharmaceutical Industry
- Electronic Industry
- Chemical Industry
- Food Industry
- Nuclear Power Plants
- Gas plants
- Paint Shops
- Computer Rooms
- Hospitals
click on the image for enlarged
view
Features
1. Frame : Cassette Type / Flange Type Standard Frames are offered in GI/MS/AL.
2. Media : Synthetic Non Woven washable sandwiched between a layer of HDPE and the Expanded mesh GI mesh for support.
3. Sealing : Sealing is done by epoxy.
Dimensions
Dimensions
610 X 610 X 150 mm & 508 X 508 X 150 mm
610 X 610 X 300 mm & 508 X 508 X 300 mm
Operating Temp.
Up to 100 oC
Operating Humidity
100% RH.
Face Velocity
1.25 m/Sec. for 150 mm thick
2.50 m/Sec. for 300 mm thick
Initial Pressure Drop
6 mm of W.G.
Final Pressure Drop
18 mm of W.G.
Test Method
Ashrae 52-76
BS 6540 / 2831
IS – 7613
Efficiency
99% down to 10 Micron
EU – Class
EU – 6
AVG. Arrestance (A)
A – 80% ≤ A > 90%